Ginlong / Solis

Ginlong Wechselrichter 4G

Auswählbar unter Bus 1,2,10 „Ginlong“

Terminierung Adressierung Schnittstelle

Terminierung Adressierung Schnittstelle
Ja Ja RS485

Bei der Geräte-Erkennung „Ginlong : 1G-4G“ auswählen.

Unterstützte Modelle:

Ginlong Solis Modelle:
  • Solis-1P1K-4G, Solis-1P1.5K-4G, Solis-1P2K-4G, Solis-1P4K-4G, Solis-1P5K-4G, Solis-1P7K-4G, Solis-1P8K-4G, Solis-1P9K-4G, Solis-1P10K-4G
  • Solis-1.5K-1G, Solis-2K-1G, Solis-2.1K-1G, Solis-2.5K-2G, Solis-2.5K-2G-ST, Solis-2.5K-4G, Solis-2.5K-4G-ST
  • Solis-3K-1G, Solis-3K-2G, Solis-3K-2G-ST, Solis-3K-4G, Solis-3K-4G-ST, Solis-3.5K-1G, Solis-3.6K-2G, Solis-3.6K-2G-ST, Solis-3.6K-4G, Solis-3.6K-4G-ST
  • Solis-4K-1G, Solis-4K-2G, Solis-4K-4G, Solis-4.6K-1G, Solis-4.6K-2G, Solis-4.6K-4G, Solis-5K-1G, Solis-5K-2G, Solis-5K-4G, Solis-5K-4G-LV
  • Solis-6K-4G, Solis-8K-4G, Solis-10K-4G, Solis-10K-4G-LV, Solis-12K-4G, Solis-15K-4G, Solis-17K-4G, Solis-20K-4G
  • Solis-3P15K-4G (mit Entwicklerfirmware), Solis-9K-4G, Solis-mini-700, Solis-mini-700-LV, Solis-Mini-700-4G, Solis-mini-1000, Solis-Mini-1000-4G, Solis-mini-1200-LV, Solis-mini-1500, Solis-Mini-1500-4G, Solis-mini-2000, Solis-Mini-2000-4G, Solis-mini-2500, Solis-Mini-2500-4G, Solis-Mini-3000-4G, Solis-Mini-3600-4G
  • Solis-6K, Solis-6K-LV, Solis-10K, Solis-10K-LV, Solis-15K, Solis-15K-LV, Solis-20K, Solis-20K-HV, Solis-20K-LV, Solis-25K, Solis-25K-LV, Solis-25K-4G, Solis-30K, Solis-30K-LV, Solis-30K-4G, Solis-33K, Solis-33K-4G, Solis-36K-HV, Solis-40K, Solis-40K-HV, Solis-40K-4G, Solis-50K, Solis-60K-HV, Solis-60K-4G, Solis-70K-HV, Solis-70K-4G

Übersicht:

  • Die Schnittstelle ist integriert.
  • Anschlussort: COM-Rundbuchsen am Wechselrichter.
  • 2-polige Verkabelung.
  • Eine Kommunikationsadresse muss vergeben werden.

Arbeitsschritte:

  1. Wechselrichter und SmartDog stromlos schalten.
  2. Wechselrichter an SmartDog anschließen.
  3. Wechselrichter untereinander verbinden.
  4. Kommunikationsadresse vergeben.
ℹ️ Hinweis: Unbedingt beachten, es gibt zwei verschiedene Verkabelungsarten dieser Ginlong-Modelle. Siehe die Verkabelungs-Tabellen weiter unten.

Wechselrichter an SmartDog anschließen

Die Verkabelung erfolgt über:

  • vorkonfektioniertes Datenkabel (im Lieferumfang des Wechselrichters)
  • selbstkonfektioniertes geschirmtes, 2-adriges Datenkabel mit Rundstecker

Vorgehen bei Modellen bis einschließlich 15K

  1. Bei selbstkonfektionierten Kabelverbindungen die Adern nach folgendem Schema anklemmen:
SmartDog RS485 (Bus 1 oder Bus 2) Wechselrichter COM1 (RS485)
A 3 RS485 A
B 4 RS485 B
GND 2 GND
  1. Rundstecker über COM1-Rundthemase des Wechselrichters verbinden.
  2. Wenn kein weiterer Wechselrichter angeschlossen wird, den Wechselrichter gemäß Anleitung zum Wechselrichter terminieren.

Wechselrichter untereinander verbinden

  • Verkabelung über Daisy-Chain-Kabel von Ginlong.
  • Verkabelung gemäß Anleitung zum Wechselrichter.
  • Letzten Wechselrichter gemäß Anleitung zum Wechselrichter terminieren.

Kommunikationsadresse vergeben

  • Empfehlung: Fortlaufende Nummerierung, beginnend mit 1.
  • Voreinstellung im Wechselrichter: Kommunikationsadresse 1.
  • Einstellung: Über Bediendisplay des Wechselrichters.
  • Vorgehensweise: Gemäß Anleitung des Wechselrichter-Herstellers.

Vorgehen bei Modellen ab 20K und größer

  1. Bei selbstkonfektionierten Kabelverbindungen die Adern nach folgendem Schema anklemmen:
SmartDog RS485 (Bus 1 oder Bus 2) Wechselrichter RJ45
A 1 RS485 A IN
B 2 RS485 B IN
GND --
  1. RJ45 in die COM2-Themase des Wechselrichters stecken.
  2. Wenn kein weiterer Wechselrichter angeschlossen wird, den Wechselrichter gemäß Anleitung zum Wechselrichter terminieren.

Wechselrichter untereinander verbinden

  • Verkabelung über Daisy-Chain-Kabel von Ginlong.
  • Anschlussort: COM-Rundthemasen am Wechselrichter.

Vorgehen:

  1. RJ45 in COM3 des Wechselrichters 1 stecken.
  2. Das andere Kabelende in COM2 des Wechselrichters 2 stecken.
  3. Weitere Wechselrichter auf die gleiche Art verbinden.
  4. Letzten Wechselrichter gemäß Anleitung zum Wechselrichter terminieren.

Kommunikationsadresse vergeben

  • Empfehlung: Fortlaufende Nummerierung, beginnend mit 1.
  • Voreinstellung im Wechselrichter: Kommunikationsadresse 1.
  • Einstellung: Über Bediendisplay des Wechselrichters.
  • Vorgehensweise: Gemäß Anleitung des Wechselrichter-Herstellers.
ℹ️ Sehr wichtig! Bitte beachten Sie für den Anschluss der Geräte des jeweiligen Herstellers die Herstellerdokumentation in der jeweils gültigen Fassung.
Ginlong Wechselrichter 5G

Auswählbar unter Bus 1,2,10 „Ginlong“

Terminierung Adressierung Schnittstelle

Terminierung Adressierung Schnittstelle
Ja Ja RS485

Bei der Geräte-Erkennung „Ginlong : 5G“ auswählen.

Unterstützte Modelle:

Ginlong Solis-5G Modelle:
  • 1P7K-5G, 1P8K-5G, 25K-5G, 30K-5G, 33K-5G, 36K-5G, 40K-5G, 36K-HV-5G, 40K-HV-5G, 50K-HV-5G
  • 15K-LV-5G, 20K-LV-5G, 50K-LV-5G, 60K-LV-5G, 75K-5G, 80K-5G, 80K-HV-5G, 90K-HV-5G, 100K-HV-5G, 110K-BHV-5G
  • 50K-5G, 50K-HV-5G, 60K-5G, 60K-HV-5G, 70K-5G, 70K-HV-5G, 75K-5G, 90K-5G, 100K-5G, 125K-HV-5G, 125K-BHV-5G
  • 110K-5G, 136K-BHV-5G, 110K-5G, 124K-HV-5G

Übersicht:

  • Die Schnittstelle ist integriert.
  • Anschlussort: Klemmblock im Wechselrichter.
  • 2-polige Verkabelung.
  • Kommunikationsadresse muss bei mehreren Wechselrichtern vergeben werden (standardmäßig steht die Adresse auf 01).

Arbeitsschritte:

  1. Wechselrichter und SmartDog stromlos schalten.
  2. Wechselrichter an SmartDog anschließen.
  3. Wechselrichter untereinander verbinden.
  4. Kommunikationsadresse vergeben.

Wechselrichter an SmartDog anschließen

Die Verkabelung erfolgt über:

  • selbstkonfektioniertes geschirmtes Datenkabel.

Vorgehen:

  1. Bei selbstkonfektionierten Kabelverbindungen die Adern nach folgendem Schema anklemmen:
SmartDog RS485 (Bus 1 oder Bus 2) Wechselrichter Klemmblock
A 1 RS485A1 IN +
B 2 RS485B1 IN -
GND --
  1. Wird kein weiterer Wechselrichter angeschlossen, den Wechselrichter gemäß Anleitung zum Wechselrichter terminieren.

Wechselrichter untereinander verbinden

  • Verkabelung gemäß Anleitung zum Wechselrichter.
  • Anschlussort: Klemmblock im Wechselrichter.

Vorgehen:

  1. Ersten Wechselrichter über RS485 Klemmblock OUT an zweiten Wechselrichter RS485 Klemmblock IN verkabeln.
  2. Weitere Wechselrichter auf die gleiche Art verbinden.
  3. Letzten Wechselrichter gemäß Anleitung zum Wechselrichter terminieren.

Kommunikationsadresse vergeben

  • Empfehlung: Fortlaufende Nummerierung, beginnend mit 1.
  • Voreinstellung im Wechselrichter: Kommunikationsadresse 01.
  • Einstellung: Über Bediendisplay des Wechselrichters.
  • Vorgehensweise: Gemäß Anleitung zum Wechselrichter.

ℹ️ Hinweis: Klemmblock beispielhaft für folgende Modelle: Solis-15K-LV-5G, Solis-20K-LV-5G, Solis-23K-LV-5G, Solis-25K-5G, Solis-25K-LV-5G, Solis-25K-US, Solis-30K-5G, Solis-30K-US, Solis-30K-5G-AU, Solis-30K-LV-5G, Solis-33K-5G, Solis-36K-5G, Solis-36K-US, Solis-36K-HV-5G, Solis-36K-LV-5G, Solis-40K-5G, Solis-40K-HV-5G, Solis-40K-US, Solis-40K-US-F, Solis-50K-HV-5G, Solis-50K-US, Solis-50K-US-F, Solis-60K-US-F, Solis-60K-HV-5G, Solis-60K-LV-5G, Solis-66K-US-F, Solis-70K-HV-5G
Zusätzliche unterstützte Modelle:
    S5-GR1P0.7K-1, S5-GR1P1K-M, S5-GR1P1.5K-M, S5-GR1P2K-M, Solis-3P5K-4G-AU-MX, Solis-3P8K-4G-AU-MX, Solis-1P6K-4G-US, Solis-1P7.6K-4G-US, Solis-1P8.6K-4G-US, S5-GR1P3.6K-M, S5-GR1P2.5K-M, S5-GR1P3K-M, S5-GR1P2.5K, S5-GR1P3K, S5-GR1P3.6K, S5-GR1P4K, S5-GR1P4.6K, S6-GR1P0.7K-M, S6-GR1P1K-M, S6-GR1P1.5K-M, S6-GR1P2K-M, S6-GR1P2.5K-M, S6-GR1P3K-M, S6-GR1P3.6K-M, S6-GR1P7K-M-LV, S6-GR1P2.5K, S5-GC25K, S5-GC30K, S5-GC33K, S5-GC36K-AU, S5-GC40K-AU, S5-GC40K-HV-AU, S5-GC50K-HV-AU, S5-GC50K IN, S5-GC60K IN, S5-GC60K-HV, S5-GC70K-HV, S5-GC25K-LV, S5-GC30K-LV, S5-GC36K-LV, S5-GC124K-HV, S5-GC124K-HV, Solis-80K-5G-PRO, Solis-110K-5G-PRO, Solis-100K-5G-PRO, GCI-230K-EHV-5G, Solis-250K-EHV-5G-PLUS, Solis-255K-EHV-5G-PLUS, Solis-185K-EHV-5G-US-PLUS, GCI-196K-EHV-5G-PLUS, GCI-215K-EHV-5G-PLUS, GCI-215K-EHV-5G-PLUS, S6-GR1P3K, S6-GR1P3.6K, S6-GR1P4K, S6-GR1P4.6K, S6-GR1P5K, S6-GR1P6K, S6-GR1P2.5K-LV, S6-GR1P3K-LV, S6-GR1P3.8K-LV, S5-GR1P7K2, S5-GR1P8K2, S5-GR1P7K, S5-GR1P8K, S5-GR1P9K, S5-GR1P10K, S5-GR1P6K, S5-GR1P7.6K, S5-GR1P8.6K, S5-GR1P8K, S5-GR1P9K, S5-GR1P10K, S5-GR3P3K, S5-GR3P4K, S5-GR3P5K, S5-GR3P6K, S5-GR3P8K, S5-GR3P9K, S5-GR3P10K, S5-GR3P12K, S5-GR3P13K, S5-GR3P15K, S5-GR3P17K, S5-GR3P20K, S5-GR3P23K, S5-GR3P25K, S5-GR3P12K, S5-GR3P13K, S5-GR3P15K, S5-GR3P5K, S5-GR3P6K, S5-GR3P8K, S5-GR3P9K, S5-GR3P10K, S5-GR3P5K-HV, S5-GR3P6K-HV, S5-GR3P8K-HV, S5-GR3P9K-HV, S5-GR3P10K-HV, S5-GR3P12K-HV, S5-GR3P15K-HV, S5-GR3P17K-HV, S5-GR3P20K-HV, S5-GR3P5K-LV, S5-GR3P6K-LV, S5-GR3P10K-LV 50K-LV-5G, 230K-EHV-5G, 185K-EHV-5G, 255K-EHV-5G, 196K-EHV-5G+, 125K-EHV-5G, 215K-EHV-5G+, 90K-5G, 100K-5G, 110K-5G, 125K-HV-5G, 125K-BHV-5G, 136K-BHV-5G, 25K-LV-5G, 60K-LV-5G, 100K-5G, 110K-5G, 125K-HV-5G, 125K-BHV-5G, 136K-BHV-5G, 110K-BHV-5G, 230K-EHV-5G+, 185K-EHV-5G+, 255K-EHV-5G+, 75K-5G, 250K-EHV-5G+, 250K-EHV-5G, 30K-5G-AU, 80K-5G, 25K-5G, 30K-5G, 33K-5G, 23K-LV-5G, 30K-LV-5G, 36K-LV-5G, 125K-EHV-5G+, 125K-EHV-5G, 104K-EHV-5G, S5-GC25K, S5-GC30K, S5-GC33K, S5-GC36K, S5-GC40K, S5-GC40K-H
Solis S6

Auswählbar unter Bus 1,2,10 „Solis“

Anschluss über BUS

Besonderheiten

TerminierungAdressierungSchnittstelle
JaJaRS485
Wechselrichter am SmartDog anschließen

SmartDog RS485Wechselrichter (RS485)
ARS485 A
BRS485 B
GNDnicht anschließen!

Die Verkabelung erfolgt über:

  • vorkonfektioniertes Datenkabel
  • selbstkonfektioniertes geschirmtes, 2-adriges Datenkabel

Übersicht:

  • RS485-Schnittstelle integriert

  • Busadresse muss vergeben werden

  • 2-polige Verkabelung

Arbeitsschritte:
  • Wechselrichter und SmartDog stromlos schalten
  • Wechselrichter an SmartDog anschließen
  • Wechselrichter untereinander verbinden
  • Kommunikationsadresse vergeben

Wechselrichter untereinander verbinden

  • Verkabelung gemäß Anleitung zum Wechselrichter
  • Letzten Wechselrichter gemäß Anleitung zum Wechselrichter terminieren

Kommunikationsadresse vergeben

Empfehlung: Fortlaufende Nummerierung, beginnend mit 1

  • Voreinstellung im Wechselrichter: Kommunikationsadresse 1
  • Einstellung: Über Bediendisplay des Wechselrichters
  • Vorgehensweise: Gemäß Anleitung des Wechselrichter-Herstellers

Einbindung

  • Bei der Wechselrichter Suche Solis auswählen

Wechselrichter einlesen per BUS RS485

Anschschluss über Netzwerk

Besonderheiten

Terminierung Adressierung Schnittstelle
JaNein Ja RS485LAN

BeiWechselrichter deram Geräte-ErkennungSmartDog „Solis“ auswählen.anschließen

Übersicht:Die Verkabelung erfolgt über:

  • Die Schnittstelle

    Netzwerkkabel ist(Patchkabel) integriert.und Ethernet-Router oder Switch

  • Anschlussort: COM-Rundbuchsen am Wechselrichter.
  • 2-polige Verkabelung.
  • Eine

    Kommunikationsadresse mussauf vergeben1 werden.stellen

Arbeitsschritte:
  • IP-Adresse statisch/fest vergeben

    1. Wechselrichter und SmartDog stromlos schalten.schalten

    2. Wechselrichter an SmartDogRouter/Switch anschließen.verkabeln (RJ45)

    3. Weitere Wechselrichter untereinander verbinden.

    4. Kommunikationsadresse vergeben.
    ℹ️ Hinweis: Unbedingt beachten, es gibt zwei verschiedene Verkabelungsarten dieser Ginlong-Modelle. Siehe die Verkabelungs-Tabellen weiter unten.

    Wechselrichterebenfalls an SmartDogRouter/Switch anschließenverkabeln (RJ45)

    Die Verkabelung erfolgt über:

    • vorkonfektioniertes Datenkabel (im Lieferumfang des Wechselrichters)
    • selbstkonfektioniertes geschirmtes, 2-adriges Datenkabel mit Rundstecker

    Vorgehen bei Modellen bis einschließlich 15K

    1. Bei selbstkonfektionierten Kabelverbindungen die Adern nach folgendem Schema anklemmen:
    SmartDog RS485 (Bus 1 oder Bus 2)Wechselrichter COM1 (RS485)
    A3 RS485 A
    B4 RS485 B
    GND2 GND
    1. Rundstecker über COM1-Rundthemase des Wechselrichters verbinden.
    2. Wenn kein weiterer Wechselrichter angeschlossen wird, den Wechselrichter gemäß Anleitung zum Wechselrichter terminieren.

    Wechselrichter untereinander verbinden

    • Verkabelung über Daisy-Chain-Kabel von Ginlong.
    • Verkabelung gemäß Anleitung zum Wechselrichter.Wechselrichter
    • Letzten Wechselrichter gemäß Anleitung zum Wechselrichter terminieren.terminieren

    KommunikationsadresseIP-Adresse vergeben

    • Empfehlung: Fortlaufende

      Es Nummerierung,muss beginnendeine mitstatische/feste 1.IP-Adresse am Display des Wechselrichters oder am Webserver vergeben werden

    • Voreinstellung

      Notieren Sie sich die vergebene IP-Adresse

    • Diese wird später für die Erkennung im Wechselrichter:SmartDog Kommunikationsadressebenötigt

      1.
    • Einstellung: Über

      Wählen BediendisplaySie deseine Wechselrichters.IP-Adresse aus demselben Klasse-C-Subnetz wie der SmartDog

    • Port auf 502 lassen

    • Beispiel:

      • SmartDog hat die IP Adresse = 192.168.178.12
      • Die Wechselrichter müssen in diesem Fall eine IP-Adresse aus dem
      • Bereich 192.168.178.xxx haben (xxx steht für eine Zahl zwischen 1 – 254)
    • Vorgehensweise: Gemäß Anleitung des Wechselrichter-Herstellers.Herstellers

    Einbindung

    • Bei der Wechselrichter Suche Solis auswählen

    Wechselrichter einlesen per Netzwerk TCP/IP

Wirkleistungssteuerung konfigurieren

VorgehenProfessional bei Modellen ab 20K und größerSetting

  1. Bei selbstkonfektionierten Kabelverbindungen die Adern nach folgendem Schema anklemmen:
SmartDog RS485 (Bus 1 oder Bus 2)Wechselrichter RJ45
A1 RS485 A IN
B2 RS485 B IN
GND--
  1. RJ45 in die COM2-Themase des Wechselrichters stecken.
  2. Wenn kein weiterer Wechselrichter angeschlossen wird, den Wechselrichter gemäß Anleitung zum Wechselrichter terminieren.

Wechselrichter untereinander verbinden

  • VerkabelungEnter über- Daisy-Chain-KabelCode: von Ginlong.0010
  • Anschlussort:Dann COM-Rundthemasenauf amFunction Wechselrichter.Setting

Vorgehen:

  1. RJ45 in COM3 des Wechselrichters 1 stecken.
  2. Das andere Kabelende in COM2 des Wechselrichters 2 stecken.
  3. Weitere Wechselrichter auf die gleiche Art verbinden.
  4. Letzten Wechselrichter gemäß Anleitung zum Wechselrichter terminieren.

Kommunikationsadresse vergeben

  • Empfehlung:Hier Fortlaufendeauf Nummerierung,More beginnendGrid mitSettings 1.
  • VoreinstellungAnschließend imauf Wechselrichter:Power KommunikationsadresseRate 1.
  • Limit
  • Einstellung: Über Bediendisplay des Wechselrichters.
  • Vorgehensweise: Gemäß Anleitung des Wechselrichter-Herstellers.

  • Hier dann ℹ️Power SehrControl wichtig!Slope Bitteauf beachten0%/min Sieeinstellen
  • für
den Anschluss der Geräte des jeweiligen Herstellers die Herstellerdokumentation in der jeweils gültigen Fassung.

Blindleistungssteuerung konfigurieren

System Setting

  • Dann auf Function Setting

  • Hier auf More Grid Settings
  • Anschließend auf Special Setting

  • Hier dann 3Tau(Q) Setting auf 0.10 S und 3Tau(P) Setting auf 0.10 S einstellen