Sigenergy Wechselrichter RS485
Auswählbar unter Bus 1,2,10 „Sigenergy“
Kompatible Typen
| Applicable model abbreviation | Model | Note |
|---|---|---|
| Hybrid Inv. | SigenStor EC (3.0, 3.6, 4.0, 4.6, 5.0, 6.0, 8.0, 10.0, 12.0) SP series | MPPT count: 2–4 PV count: 2–4 |
| Sigen Hybrid (3.0, 3.6, 4.0, 4.6, 5.0, 6.0) SP | MPPT count: 2–4 PV count: 2–4 |
|
| Sigen Hybrid (5.0, 6.0, 8.0, 10.0, 12.0, 15.0, 17.0, 20.0, 25.0, 30.0) TP series | MPPT count: 2–4 PV count: 2–4 |
|
| SigenStor EC (5.0, 6.0, 8.0, 10.0, 12.0, 15.0, 17.0, 20.0, 25.0, 30.0) TP/TPLV series | MPPT count: 2–4 PV count: 2–4 |
|
| Sigen PV (50, 60, 80, 100, 110, 125) MI-HYA series | MPPT count: 4–8 PV count: 8–16 |
|
| PG Controller (3.8, 4.8, 5.7, 7.6, 9.6, 11.4) series | MPPT count: 2–4 PV count: 2–4 |
|
| PV Inv. | Sigen PV Max (3.0, 3.6, 4.0, 4.6, 5.0, 6.0) SP | MPPT count: 2–4 PV count: 2–4 |
| Sigen PV Max (5.0, 6.0, 8.0, 10.0, 12.0, 15.0, 17.0, 20.0, 25.0) TP | MPPT count: 2–4 PV count: 2–4 |
|
| Sigen PV (50, 60, 75, 80, 99.9, 100, 110, 125) MI series | MPPT count: 4–8 PV count: 8–16 |
Besonderheiten
-
Auswählen unter Sigenergy
-
Kommunikationsschnittstelle integriert
-
Busadresse muss vergeben werden. Mit BUS Adresse 1 beginnen.
-
Baudrate: 9600
-
Protokoll: Modbus
-
2-polige Verkabelung
-
Wird nur ein Wechselrichter angeschlossen, muss dieser terminiert werden. Werden mehrere Wechselrichter angeschlossen muss der letzte Wechselrichter terminiert werden.
Vorgehen
-
Wechselrichter und SmartDog® stromlos schalten
-
Wechselrichter 1 mit SmartDog® verkabeln
-
Wechselrichter 2 und weitere Wechselrichter verkabeln
Bitte beachten Sie die Anschlusshinweise des Herstellers genau!
Einstellungen am Wechselrichter
Für die korrekte Kommunikation muss folgendes parametriert werden